Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameDRURY INN & SUITES POOL
Address415 W W T HARRIS BLVD
 
City/State/ZIP
CHARLOTTE NC 28262
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 1/11/2022
Final Score @ Grade
18
General CommentsFacility has a CPO, but he was not present today. Immediate suspension issued due to cloudy water.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
1 6 Water quality: water clear enough to clearly see bottom of pool and pool drain No No No .2535(2) Main drains must be clearly visible from the pool deck. Pool is cloudy and drains are difficult to see from certain areas of pool deck. *Immediate suspension item
5 4 Water quality: daily written records of water quality and test kit kept on site No No No .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Entries for cyanuric acid and total alkalinity are missing for the past month.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No .2518(k) Surface skimmers shall be installed per manufacturer's instructions. Skimmer baskets are incorrect size and have rocks in them. Skimmers shall be designed and constructed in accordance with section 8 of NSF Standard #50. // .2518(k) Replace missing weirs. Weir missing in 1 skimmer basket.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No .2521 Install ladders per manufacturer instructions. 1 ladder missing end cap and another missing tread.
27 2 Equipment room: filter backwash discharged through an air gap No No No .2513(b) Filter backwash shall be discharged through an air gap. Air gap missing on back wash.