Water quality: pool water pH |
No |
No
|
No |
pH 7.1. .2535(1) Maintain pH at 7.2 to 7.8. - Corrected to 7.2. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Facility does not have a CPO on staff to check the pool every day. .2537(c) Pool owner shall provide for the operation and maintenance of the pool by a trained pool operator. - Intent to suspend item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Some skimmer baskets are the wrong size. .2518(k) Skimmers shall be designed and constructed in accordance with section 8 of NSF Standard #50.
Maintenance vacuuming through the skimmer. Pool built with Integral vacuum system. .2518 (f) Vacuum the pool through the integral vacuum system. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Some ladders loose. One missing an endcap. .2521 Install ladders per manufacturer instructions.
Ladder missing non-slip tread. .2521(b) Ladders shall have slip-resistant tread.
Escutcheon plate missing on handrail. .2521 Install handrail per manufacturer instructions. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Some chairs too close to pool edge. .2522(a) Provide 6 ft of clear walking space around the pool at all times for outdoor portion of pool. - Corrected
Some chairs too close to pool edge. .2522(b) Provide at least 5 ft of clear walking space around the pool at all times for indoor portion of pool. - Corrected. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Emergency phone not functioning. .2530(f) Emergency phone shall remain operable. - Corrected.
Incorrect dialing instructions posted, phone number not posted. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. - Corrected. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap for backwash. .2513(b) Filter backwash shall be discharged through an air gap. |