11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
One loose handrail on ladder.
.2521 Install ladders per manufacturer instructions. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Permit restriction on pump not to exceed 225 gpm. Flow meter indicating 320 gpm. Flow shall not exceed permit restriction due to sizing of filter. Intent to Suspend issued.
.2518(h) Provide approved pump in good repair. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Check valve leaking in pump room above filter. Pump room floor wet.
.2533(d) Pump room floor shall be kept dry and free of standing water. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Leaking faucet handle in women's restroom.
.2626(m) Keep restrooms and fixtures clean and in good repair. |