9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
7 ft. 4 in depth marker on side closest to pump room coming off of wall. Replace depth marker. 6 ft. 9 in. with N missing some of the lettering on right side of pool near lane flag. Depth markers shall be 4" height. Intent to Suspend issued. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Slip-resistant tread beginning to wear off of some starting platforms. Monitor and replace where needed.
No labeling on diving boards. .2517 Diving equipment shall be installed in accordance with Rule .2517.
Warning signage peeled off on multiple dive platforms. Dive platforms shall have warning signage along with constant monitoring from lifeguard. Replace warning signage on platforms or provide other means to keep inaccessible.
Bulkhead with some damage to slip-resistant tread. Monitor and repair as needed if worsens. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Most double doors at family dressing rooms and also double doors to main entrance dog-eared back. Doors shall self-close, self-latch. Double doors that lead to outside at deep end of pool not self-closing, self-latching. Appears that weather stripping is preventing doors from latching. Rooms 114 and Ste 12 with either audible alarms not operable or not latching. All doors shall self-close, self-latch. Intent to Suspend issued. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Cap missing from pool deck at far end of pool. Replace cap. No openings/offsets >1/2". Intent to Suspend issued. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Check valve for fill line leaking. Catch drain leaking. Floor wet under leak. Keep floor dry. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Cold water handle in the women's locker room damaged. Repair. |