Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameDOUBLETREE HOTEL
Address2600 YORKMONT RD
 
City/State/ZIP
CHARLOTTE NC 28208
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 8/16/2023
Final Score @ Grade
14
General CommentsInspection conducted with operator Andy. All non-compliant items corrected during inspection. Note: CYA readings approaching 100ppm. Correct to ensure proper pool chemistry and continuation of effective disinfection. Night swimming remains approved.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Accumulated debris in skimmers. Cleaned during inspection.
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy rope exceeding 19’. Operator corrected to required 18’.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Chemicals stored in pump room. Items around equipment and piping. Pool built '89. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. Dry chemicals stored directly on floor. .2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
27 2 Equipment room: filter backwash discharged through an air gap No No No No air gap at pool backwash. Pool built 1989. .2513(b) Filter backwash shall be discharged through an air gap.