Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Test kit with black residue on bottom of cyanuric acid test tube. Replace test kit as needed.
.2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
One ladder closest to fitness area with rungs 9" to pool wall. Maintain 3" to 6" between wall and ladder rungs. Pool built 1989.
.2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
One return missing fitting. Replace return fitting.
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy rope at 16 ft. due to tie off. Corrected to 18 ft. during inspection.
General Comment - Grab rope on ring buoy starting to degrade. Still usable. Replace within 30 days. A return visit will be made in 30 days to verify if documentation not provided. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
New chlorinator installed - CCH Endurance - located at entry to the pump room. Provide 3 ft. clearance around all equipment. Operator indicated that Leslie's Pools has already been contacted to move chlorinator.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
Some piping not labeled in pump room.
.2518(d) Piping and valves shall be labeled with color codes or labels. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap at backwash line to pit. Pit is half full of water.
.2513(b) Filter backwash shall be discharged through an air gap. |