Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
New drain covers installed. Left side, lower left missing Aquastar star and appears to be installed backwards. Not flush to wall. Used body hook to ensure still secure. Drain cover shall be flush. Verify installed per mfg. instructions. Does not appear to look like 24xxx with horizontals and verticals. Given one week to correct or permit will be suspended. If not installed backwards, missing piece of product and should be replaced.
Some screws appear to be loose in both sets of drain covers. Tighten screws per mfg. instructions. Given one week to correct or permit will be suspended. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Multiple drains around pool with either missing screws and not secure or rusted screws. Replace screws and secure where needed. Intent to Suspend issued. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter stuck. No permit restriction. Keep flow meter operable. Was not able to verify flow of system. Intent to Suspend issued. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
One sink slow draining in women's restroom. Keep all fixtures in good repair. |