16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Back door not self-latching at time of inspection. Door from aquatic supervisor office, into guard room, with 2 additional doors onto pool deck has alarm, but does not self-close.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
**30 Day Intent to Suspend (ITS). Contact Marie Daley at 704-507-6806 when corrected to lift ITS. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Benches within 5' of pool. .2522(b) Provide at least 5 ft of clear walking space around the pool at all times.
**30 Day Intent to Suspend (ITS). Contact Marie Daley at 704-507-6806 when corrected to lift ITS. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
No spare pump basket. Pool built in '87. No longer able to find. No ITS issued for this item.
.2518(e) Provide a spare basket for pump. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals stored in pump room. Pool built in '87.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |