| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some algae on step ladders outside. Keep walls/fixtures in good repair and free of slip hazards. Algae in corners of ladder rungs and not on tread. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
One ladder (indoor) missing end cap bumper on ladder. Replace to eliminate damage to plaster. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Outdoor throw rope tangled. Corrected during the inspection. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528 Pool fencing does not meet rule requirements. Pool built prior to 2010. Observed >4" between horizontals. Perimeter fence on indoor at 42" in height with footholds. Perimeter gates swing into pool. Gates with horizontals at >30" meeting code exception requirement at 30" to 45" between horizontals since pre-2010. Exterior barrier with decorative features that provide footholds. Outdoor portion of pool contains separate gate that also does not meet code requirements. Gate leads to additional space which is fenced in with barrier that does not meet code requirements. See reference above. Gate is locked shut. Main gate entry into pool area leads into pool deck due to handicap ramp and handicap accessibility. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Some algae on pool deck around 3 ft. depth marker (indoor). Keep decking free of algae.
Some damage to coping on left side of pool near pillar (indoor). Offsets not greater than 1/2". Recommend patching.
Pool furniture directly behind pillar. Furniture shall not be located on pool deck behind decorative features so that any part of the interior of the pool is blocked. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
Warning sign missing from exterior pool area. Provide "Warning - No Lifeguard on Duty" in 4" lettering. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
One outdoor perimeter pool light burnt out. Replaced during the inspection.
Pool due for night swimming renewal. A site visit will be made week of March 9th for verification prior to sunrise. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Phone not operable. Phone not connecting to 911. Phone shall connect to 911. 911 shall have the correct address and phone number. Phone shall audibly ring or answer automatically when number dialed. Immediate suspension issued. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
No flow meter on chlorinator. Original construction. If repaired/replaced, install per NSF requirements. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter for indoor pool stuck. Permit restriction that flow meter must remain operable, reading no greater than 20 gpm due to return number restriction. Repair flow meter so operable with flow reading 20 gpm. Operator replaced flow meter while onsite; however, will verify on return visit to reopen the pool. Repeat issue with flow meter. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Pump room floor wet due to leak at one of the boilers. Equipment does not appear to be leaking. Keep pump room floor dry. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib and floor drain in restrooms. Original construction. Provide hose bib and floor drain. |