16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528 Pool fencing does not meet rule requirements. Pool built prior to 2010. Observed >4" between horizontals. Perimeter fence on indoor at 42" in height with footholds. Perimeter gates swing into pool.
Per pool operator gates are ADA access gates. Pool gates prior to 2010. Per operator, battery back-up installed at gates. One gate leads to handicap ramp for ADA accessibility. One gate leads to step and leads into pool. Gate shall swing away from the swimming pool and self-close, self-latch. Provide documentation that gate with steps is required for egress to swing into the pool. If not, gate shall be repaired prior to May 1, 2024 operating permit.
Outdoor portion of pool contains separate gate that also does not meet code with same observations. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Some sealant on decking chipping up. Continue to monitor. May require repair in the future if worsens. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Leak at chlorinator valve. Repair leak.
No flow meter on chlorinator. Original construction. If repaired/replaced, install per NSF requirements. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not operational on indoor pump. Required flow restriction at 20 gpm. Could not verify flow. Replace flow meter with operable flow meter. Intent to Suspend issued. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib and floor drain in restrooms. Original construction. Provide hose bib and floor drain. |