| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No temperature logs. Per operator, heater was just turned on in last week. Maintain daily record keeping for temperature once heater is in use. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
New pump installed. Did not submit in-field plan review application. Numbers run during inspection. Limiting factor is # of returns. Flow meter was not operable at time of inspection. Pump turned down to the lowest rpm setting at 1400 rpm with a max flow of 40 gpm and design appears to be about 15 gpm. Flow meter required operable with max flow at 20 gpm due to return number restriction. Return visit required to verify after flow meter is repaired. Electrical permit - e4200152. Return visit will be made on 10/12 to verify flow meter setting and operable. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One outdoor skimmer missing weir. Replace weir. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
One outdoor ladder loose. Keep ladders in good repair. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Door to fitness room not self-latching. Repair to self-latch. Intent to Suspend issued.
.2528 Pool fencing does not meet rule requirements. Pool built prior to 2010. Observed >4" between horizontals. Perimeter fence on indoor at 42" in height with footholds. Perimeter gates swing into pool. Per pool operator gates are ADA access gates. Pool gates prior to 2010. Per operator, battery back-up installed at gates. Outdoor portion of pool contains separate gate that also does not meet code with same observations. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Some damage to decking on outside deck and also inside near the 3 ft. depth marker. Keep decking in good repair. Repair where needed. Intent to Suspend issued. Deck requires permanent repair prior to 2023 operating season.
Some standing water to left of step handrail near drain. When deck repaired, ensure no standing water. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
No flow meter on chlorinator. Original construction. If repaired/replaced, install per NSF requirements. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not operable. Required operable due to permit restriction. RPM setting must be set so that flow meter reads 20 gpm. Ensure flow meter is installed correctly with 5x pipe diameter on inlet side and 2x pipe diameter on outlet for a Blue White flow meter. Intent to Suspend issued. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib and floor drain in restrooms. Original construction. Provide hose bib and floor drain. |