| CDI=Corrected During Inspection | |
R=Repeat Violation | |
VR=Verification Required | |
|
|
| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
New pump installed. Numbers run while in field and approved with new pump SF-N1-1 1/2A, 1.5 hp pump. Meets restrictions of pump room. Electrical inspection passed September 2021. New pdsc form filled out while onsite.
For any future pump changes, submit in-field plan review application with updated pdsc form. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some algae on pool walls. Continue to monitor and treat as needed. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One skimmer weir missing on outside pool. Install weir. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder furthest from phone loose and missing end caps. Secure and replace end caps. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528 Pool fencing does not meet rule requirements. Pool built prior to 2010. Observed >4" between horizontals. Perimeter fence on indoor at 42" in height with footholds. Perimeter gates swing into pool. Per pool operator gates are ADA access gates. Pool gates prior to 2010. Per operator, battery back-up installed at gates. Outdoor portion of pool contains separate gate that also does not meet code with same observations. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Damage to deck in two locations and sharp edge near skimmer. Repair deck. Intent to Suspend issued. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
No flow meter on chlorinator. Original construction. If repaired/replaced, install per NSF requirements. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
New pump installed. Provide spare pump basket. Intent to Suspend issued. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib and floor drain in restrooms. Original construction. Provide hose bib and floor drain. |
|