5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Temperature logs not maintained. Maintain daily temperature logs. Intent to Suspend issued. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
27 ft between depth markers on wall at shallow near pump room. 32.5 ft between wall depth markers at deep end. Assure depth markers maintained 25 ft apart or less in 4" lettering. Depth marker sticker worn off at 6 ft 3 in. Replace to maintain 4" height requirement and contrasting. Intent to Suspend issued for both items. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
One ladder handrail loose. Keep tightened. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Fixtures holding one main drain into place rusted. Keep fixtures in good repair. All fixtures shall be stainless steel in pool. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
One door on to deck not latching when closing. Restroom doors and double doors not self-closing, self-latching. Repair to self-close, self-latch or provide audible alarm at entry points. Intent to Suspend issued. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Observed deck near pump room with rust and some build-up on deck. Keep clean and in good repair. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Lights not operable in pool. For night swimming, lights shall be operational or main drains must be clearly visible at all times including all areas of pool deck. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Filter leaking and flow meter not operational. Repair filter (was being repaired during inspection) and keep flow meter operational. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Light burnt out and forced ventilation not operable in chemical storage room. Repair light and maintain continous forced ventilation in chemical storage room. |