Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameALEXANDER YOUTH NETWORK
Address6220 THERMAL ROAD
 
City/State/ZIP
CHARLOTTE NC 28211
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 9/23/2026
Final Score @ Grade
12
General CommentsLifted suspension and conducted inspection. Flow reading approx 90 gpm at time of inspection. Flow required 99-110 gpm. Operator adjusted pump speed and backwashed for 99 gpm. Monitor readings and ensure flow is being met for proper operation/turnover of pool. Sump pump is required. Placed in “A” Open for Business Discussed if changes are made in future (like plastering and/or adding steps), submit in-field plan review to Health Dept PRIOR to changes being made for approval. Mainline fort Health Dept is 980-314-1620 and/or visit website https://eh.mecknc.gov/pools

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Weirs installed upside down. .2518(k) Replace missing weirs. Operator adjusted and corrected.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Operator unable to locate spare pump basket at time of inspection. .2518(e) Provide a spare basket for pump. Lack of severity does not warrant permit action. Operator ordering spare pump basket, pump is Pentair Intelliflo VSF 011056
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Items within 3’ of pump and equipment. Chemicals stored in pump room. Pool built in 1966. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Restroom renovation with painting being finished. Fixtures and items removed from area until complete. Operator will replace after renovations are complete. No structural changes made. .2526(l) Provide toilet paper and dispensers in restrooms. .2526(m) Keep restrooms and fixtures clean and in good repair.