16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Door entry from hallway to pool deck does not fully self-close/latch. Audible bell present but located such that it does not always alert. CDI- bell relocated such that it rings with each entry. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2522(b) Provide at least 5 ft of clear walking space around the pool at all times. Observed pool noodle storage not in use within 5’ of pool. CDI - relocated away from pool. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Automatic feeder not shutting off with pump.
.2535 Automatic acid and chlorine feeder shall be automatically prevented from operating when the circulation pump is not in operation. Observed that pump had debris in pressure switch causing it to not fully turn off when pump disabled. CDI - cleaned out - - observed to close properly. Ensure acid feeder shuts off every time that pump is disabled. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
No spare pump basket for pump. Pool built in '66, spare basket not available for pump to purchase.
.2518(e) Provide a spare basket for pump. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Water on pump room floor. .2533(d) Pump room floor shall be kept dry and free of standing water. .2533(d) Pump room floor shall be sloped to drain. Note: small leak from pump operator noted will be corrected in March 2023.
Chemicals stored in pump room. Pool built prior to 2004 (1966). .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.253 |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap at backwash. Pool built 1966. .2513(b) Filter backwash shall be discharged through an air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in special needs dressing room showers as high as 123f at time of visit. .2526(i) Water in restrooms shall not exceed 110 F. |