Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Back door not latching or alarmed at time of inspection. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. *30 Day Intent to Suspend (ITS) item. Contact Marie Daley 704-507-6806 when corrected to lift ITS. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
911 callback number not designated line at time of visit (calls back to main line with no reference to pool). Signage reads 9-911, dialing observed was directly dialing 911.
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone.
IT repaired the phone to call on designated line, displayed correct number, called back correctly and signage was corrected with dialing instructions. Corrected. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
No spare pump basket. Pool built in 1966, spare basket not available for pump to purchase. .2518(e) Provide a spare basket for pump. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals stored in pump room. Water under pump and on pump room floor. Pool built prior to 2004 (1966). .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.253
.2533(d) Pump room floor shall be sloped to drain.
.2533(d) Pump room floor shall be kept dry and free of standing water. |