Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameYWCA OF THE CENTRAL CAROLINAS
Address3420 PARK ROAD
 
City/State/ZIP
CHARLOTTE NC 28209
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 2/5/2020
Final Score @ Grade
18
General CommentsITS for back door self-closing, self-latching or audible alarm. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS. Main drains expire March 2020. Update and submit updated PDSC form for approval prior to expiration. Failure to update main drains and PDSC will result in permit action and permit will not be issued for 2020.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No Total alkalinity not recorded weekly. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator checked and corrected.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No One ladder rail loose by diving boards. Keep tight and in good repair.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Back door not latching and door not alarmed every time open (alarm only works intermittently) .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. *30 Day Intent to Suspend (ITS) item. Contact Marie Daley 704-507-6806 when corrected to lift ITS.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No No spare pump basket. Pool built in 1966, spare basket not available for pump to purchase. .2518(e) Provide a spare basket for pump.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Chemicals stored in pump room. Pool built prior to 2004 (1966). .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Hot water in shower over 110 degrees F at time of visit. .2526(i) Water in restrooms shall not exceed 110 F.