Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameYMCA JOHNSTON
Address3025 N DAVIDSON ST
 
City/State/ZIP
CHARLOTTE NC 28205
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 9/10/2019
Final Score @ Grade
26
General CommentsIntent to suspend issued for record keeping for alkalinity, door on to pool deck self-closing, self-latching, and operational flow meter.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No Pool pH at 7.0. Required at 7.2 to 7.8. Corrected to 7.2 during inspection.
5 4 Water quality: daily written records of water quality and test kit kept on site No No No Alkalinity not recorded weekly. Record weekly. Intent to Suspend issued.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No One door not self-closing, self-latching. Getting stuck when opened. Located near locker room entry. Repair to self-close, self-latch. Intent to Suspend issued.
18 4 Premises: lifeguards present or warning signs posted No No No Some standing water on pool deck next to pool coping. Did not notice any build-up below water. Continue to monitor and keep deck free of standing water.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Flow meter not operational. Repair to operational. Intent to Suspend issued.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Floor in pump room/chemical storage room wet due to backwash of pump. Open pipe on side of backwash pit that allows overflow of water on to pump room floor which drains to chemical storage room. Keep pump room floor dry.
31 2 Dressing and sanitary facilities: sewage disposed of in a properly operating sewage system No No No Backwash water goes directly to drain without air gap. Install air gap or approved backflow prevention/check valve. Water line check valve does not meet .2512. If ever replaced, replace with approved check valve. Original construction.