Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(b) Pools with single main drain or drains <36" apart shall provide a safety vacuum release system (SVRS) or other methods of preventing bather entrapment. Observed Vac-Alert on aeration pump not functioning due to clogged filter. CDI-filter replaced, Vac-Alerts working properly |
|
14
|
4
|
Pool maintenance: spa timer working properly |
No |
No
|
No |
.2537(b) Spa times shall not exceed 15 minutes without manual resetting. Observed timer did not turn off for 17 minutes. CDI-screw put in, timer stopped at 7.5 minutes. Make sure timer does not exceed 15 minutes. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer. Observed no backflow preventer at hose bib on pool deck. |