Water quality: disinfectant residual provided by |
No |
No
|
No |
Observed chlorine level at 1.5 ppm. Granular chlorine was add to the skimmer basket to raise level to 2.0 during inspection while no bathers were in the pool. Ensure Chlorinator is working properly in the pump room and 2.0 ppm chlorine level is maintained during all hours of operation. Chlorinator had a puck inside and was set to the highest setting. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Fan in chemical room was not working and there is not continuous or cross ventilation. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Glass mirrors are installed in both restrooms. |