Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Observed PDSC information for the feature and the filtration main drains do not match. PDSC forms state Aquastar A10, however in the wading pool observed Paramount SDX2’s for both. Resubmit PDSC forms to the department fro approval prior to permit issuance. Permit Denial. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed only dial instructions with the emergency phone. CDI. - CPO provided address and telephone number at the emergency phone. |