Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Flow meter be capable of measuring 1.5 times the design flow rate. Observed flow meter on return line that is not capable of measuring 1.5 times the design flow. Flow meter measures to 120 GPM and is showing a flow reading that appears to exceed that flow rate. Install a proper flow meter.
.2518(g) Install flow meter on return line per manufacturer instructions. Observed a second flow meter that is not installed per manufacturer instructions. Install properly. |