3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 7.0. CDI - Increased to 7.4 |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(b) Pools with single main drain or drains <36" apart shall provide a safety vacuum release system (SVRS) or other
methods of preventing bather entrapment. Observed SVRS system disconnected upon inspection. PIC installed and tested and
verified working condition. EHS recommends keeping manufacturers instructions and manual present in pump room.
.2539(c) The operator of the public swimming pool shall test an installed safety vacuum release system using the methodology
and at the frequency recommended by the manufacturer, and the test dates and results shall be recorded in the written records
required by Rule .2535(11) of this Section. Observed no logs for SVRS system. Observed SVRS system disconnected. PIC
connected system and verified working condition. BE SURE TO REGULARLY TEST SVRS SYSTEM PER MANUFACTURER
INSTRUCTIONS. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
.2537(14) Keep pool surface and pool floor free of debris. Observed slight debris present on pool floor. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. observed slight debris
present in skimmers. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Provide signage with location of emergency phone if not visible from all areas inside pool enclosure. Observed
emergency phone not located in a visible area from all areas of the pool and no signage pointing to it. PIC provided handwritten
signage to provide location. Provide more permanent signs. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. Observed no cross ventilation in
chemical room. |
|
26
|
2
|
Equipment room: valves and pipes identified by color codes or labels |
No |
No
|
No |
.2518(d) Piping and valves shall be labeled with color codes or labels. Observed piping with fading labeled piping. Re label. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. Observed backwash through air break only. |