Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 7.1, PO corrected pH to 7.3 with soda ash. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Keep flow meter operational. Flow meter stuck, not operating. Flow meter was replaced with proper working flow meter. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. Hose bibs outside of clubhouse need backflow prevention devices.
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Chemical storage room ceiling forced ventilation not functioning. Not enough ventilation for natural cross ventilation. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. Backwash is directly plumbed, no air gap.
General Comment: Permit Issued |