16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2537(b) All gates and doors shall be self-closing, self-latching.
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present. Observed all 3 access gates that are not self-closing self latching. Only one gate is constantly monitored by an attendant. Other 2 access gates are not monitored, but per CPO are constantly locked. Gate to left of pool house does not have a latch. Observed maintenance gate that does not self close or self latch. Per Sr. EHS C. Sells, permit for 2022 will be issued with conditions regarding gates remaining locked. Gates must be self closing, self latching before permit is to be issued for the 2023 operation year.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed door from pool house does not self-close, self-latch or have a working audible alarm. CDI: Door was made self closing and alarmed During inspection. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Provide signage with location of emergency phone if not visible from all areas inside pool enclosure. Observed no signage indicating phone location in pool house. CDI: Signage posted. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
. 2533(d) Pump room floor shall be kept dry and free of standing water. Standing water observed in pump room. REPEAT VIOLATION
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Observed no forced or cross ventilation in pump room |