2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Chlorine 1.0 ppm at time of inspection.
.2531(a) Maintain chlorine in wading pools or children activity pools at least 2.0 ppm. Operator corrected to 3.0 ppm. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Wading pool gate not latching at each closure at time of inspection.
.2537(b) All gates shall be self-closing, self-latching.
Operator corrected to self-close, self-latch. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals stored in pump room. No 3’ space around equipment. Pool built 1990. .2534(2) Pools constructed after April 1, 2004
shall provide a separate room for chemical storage meeting Rule.2534.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump
room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water over 110 F in restrooms.
.2526(i) Water in restrooms shall not exceed 110 F. |