17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed planter closer than 6ft to pool. Relocated. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Signage advised to push call box button. There is no call box. That part of sign was covered and "Pick up phone" was added to reflect proper instructions (no dialing needed at this phone). |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2534 Provide sufficient lighting in chemical storage room. Provide continuous forced ventilation or cross ventilation in chemical storage room.
Chemical/pump room does not have working lighting and no cross/forced ventilation. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
.2626(i) Water in restrooms shall not exceed 110 F. Restroom hot water was 113F. |