16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm.
Observed an audible alarm detached from one inside window. CDI - Alarm was reattached during inspection.
Observed one ground level door (far side office room) without an audible alarm. CDI - Door was permanently locked until an alarm can be installed.
All other windows and doors contain and audible alarm or permanently screwed shut. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
Observed broken ventilation system in the pump room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
.2526(i) Water in restrooms shall not exceed 110 F.
.2526(k) Provide shatterproof mirrors.
Observed 115 degree water in the restroom sinks. Observed glass mirrors in the restrooms. |