2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Maintain chlorine at least 1ppm. Observed at .7 at time of arrival. CDI-Observed at 2ppm before leaving. Also observed chlorine tablet in skimmer basket. CDI by instruction-tablet removed. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
Maintain pH at 7.2 to 7.8. Observed pH at 6.8 upon arrival. CDI-chemicals added. Observed at 7.2 before leaving. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Maintain daily records of chlorin, pH and main drains and weekly records of total alkalinity and cyanuric acid. Observed no records on site. ITS issued. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Maintain equalizer covers in place on pool wall. Observed one cover missing. CDI- cover was in pump room and replaced on wall during inspection. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Observed one of two weirs missing. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
Provide depth markers on pool wall and pool deck at least every 25ft. Observed only 5ft markers in place on pool wall. Observed more than 25ft spacing (no 3ft or 8ft) markers observed on pool wall. ITS issued. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Provide fittings in place as needed. Observed all return line fittings missing. Observed vacuum line with out plug but turned off. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Rope for ring buoy must be 33ft. Observed rope tangled/knotted and when untangled only 27 1/2ft. CDI- new rope obtained and tied to ring buoy. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Observed pump room with less than 7ft height ceiling. No ventilation in pump room/chemical room. |