Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Skimmer weirs missing from both. CDI- Operator replaced both immediately. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Rope attached to ring buoy less than 30.0Ft. Measured at 23Ft twice. CDI-Operator corrected immediately/ replaced ring buoy and rope. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Piping attached to side wall next to side pool deck gate that would allow for a foothold. Piping is not located close to or at the gate entrance to pool. Correct to not allow possible foothold. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Three of four lights out at pool deck. Posted pool hours indicate 9a-10p; and both operator and facility engineer advised that hours are correct. CDI- Lighting was repaired/ replaced. |