Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(d) All drain covers shall be kept in good condition. Missing, broken, or cracked fittings shall be replaced or reattached before the pool should be used. Observed 3 incorrect equalizer covers installed. Current equalizer covers installed did not match what was documented on PDSC submitted by operator. CDI: correct equalizer covers where located inside pump room and installed during inspection to match up with what was submitted on paperwork. |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
.2523(c) Depth markers shall be 4 inches in height and of a contrasting color with the background, clearly visible. Observed two 4 foot depth markers on pool deck that were faded and not clearly visible. CDI: depth markers were spray painted over during inspection and now clearly visible. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed vacuum line cover missing however vacuum was not in use and not turned on. CDI: vacuum line plugged during inspection. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed rope length greater than 50ft. CDI: shortened to 50ft during inspection. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Provide no openings in fence and/or gate greater than 4". Observed some openings in between fence spigots > 4". No permit action. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(a) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed no address or phone number posted at emergency phone. CDI: address and phone number provided and posted during inspection. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Keep flow meter operational. Observed flow meter not working. CDI: repaired during inspection and now working properly. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. Observed no air gap on backwash line. CDI: air gap provided. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
.2626(m) Keep restrooms and fixtures clean and in good repair. Observed cracked floor tile around floor drain in women's restroom. |