Premises Information

Return to Inspections
NameVISTA COMMONS APTS
Address2728 COMMONWEALTH AVE
 
City/State/ZIP
CHARLOTTE NC 28205
Premise Type50 - Seasonal Swimming Pool
CountyMecklenburg
Inspection Date 6/5/2024
Final Score @ Grade
12
General CommentsNo night swimming. Permit Restriction: Flow meter must remain operable. Flow shall not exceed 138 GPM due to drain Cover Flow restriction.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed skimmer baskets with debris. CDI: Baskets emptied. REPEAT VIOLATION
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed doors alarms not functioning and doors are not self closing. CDI: Alarms provided during inspection. Per guidance from C. Sells, door closers to be provided within 2 weeks. EHS A. Hall will follow up.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. Natural cross or continuous forced ventilation required; store chemicals off the floor. REPEAT VIOLATION
27 2 Equipment room: filter backwash discharged through an air gap No No No .2513(b) Filter backwash shall be discharged through an air gap.Observed no air gap on backwash line. REPEAT VIOLATION