| CDI=Corrected During Inspection | |
R=Repeat Violation | |
VR=Verification Required | |
|
|
| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
Observed the pH at 7.0. CDI- Soda ash added. pH at 7.2 now. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Observed only pH, chlorine, and main drains checked for the month. Ensure to check the Total Alkalinity & Cyanuric Acid weekly |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Observed debris in the baskets. Clean. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Observed an end cap missing on a ladder. Provide. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
-Observed the buoy rope at 32 feet. CDI- Purchased new and cut to 36 feet.
-Observed the ring buoy and the body hook hanging behind/between 2 tree bushes. Not visible from pool. CDI- Relocated to a visible and accessible place. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Observed the gate by the pump room not self closing/self latching. CDI- Tightened- Closing now. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Observed chairs 4.5-5 feet from the pool edge. CDI- Pushed back to provide the 6 feet minimum. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Observed the flow meter weight stuck. CDI- Fixed- floating now. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Observed the pump room floor wet. Keep dry.
Per Jovany, no night swimming.
Permit provided #18-600638 (county); 2060501215 (state)
Report emailed to jrivera@weinsteinproperties.com |
|