Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. - Observed pH between 8.0-8.2 in multiple areas of pool. One area of pool read 7.4 pH. Pool must have pH between 7.2-7.8 throughout entire pool. CPO was unable to correct pH. Permit denied until pH can be corrected. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. - Observed no weekly total alkalinity checks in log books. - CDI - CPO checked total alkalinity during inspection. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs. - Observed one missing weir; 2 out of 3 present. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(g) Keep flow meter operational. - Observed electric flow meter installed but not operational. CPO unable to fix electric flow meter. Repair or replace flow meter. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. - Observed open bags of dry chemicals stored directly on the floor. Keep chemicals off the floor. Place dry chemicals in a protective container. |