3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535 Chemicals shall be 1 ppm in the pool and 7.2-7.8pH levels. Observed chlorine at 0ppm and pH below 6.8. Immediate suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535 Check total akalinity and cyanuric acid on a weekly basis. Observed 23 days pass before cyanuric acid was checked. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539 Proper documentation needs to be sent in regarding information on drain and equalizer covers. Observed PDSC form stating they have Waterway 640-4790v but saw Aquastar WAV9WRxx. Facility must resubmit new PDSC forms for approval. Immediate suspension issued. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518 skimmers shall be kept in good repair. Observed weirs missing from all 4 skimmers. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518 Keep flow meters in good repair. Observed flow meter that was not in good repair. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533 and .2534 Keep proper ventilaiton in equipment and chemical storage room. Observed internal ventilation that was not providing air flow in equipment/chemical room. |