Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(b) Pools with single main drain or drains <36" apart shall provide a safety vacuum release system (SVRS) or other methods of preventing bather entrapment. Observed two openings in pool wall near swim out. Both openings have plastic inset niches iwth no openings for suction or return yet present a potential entrapment hazard. Staff contend they have never been covered. Corrected onsite-Swim Club Mgt. able to find Hayward equalizer covers to fit the openings; installed. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
.2537(14) Keep pool surface and pool floor free of debris. Observed leaf debris in pool |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed heavy debris in gutters |
|
10
|
2
|
Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints |
No |
No
|
No |
.2523(e) Provide a minimum of 3/4 inch diameter safety rope at the breakpoint. Observed no safety rope installed at the breakpoint. CDI- installed |