Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. - Observed the PDSC form stating the facility has 8 Aquastar 6 HPHAs installed but they had 6, 4 HPs and 2, 6 HPs installed. CDI (corrected during inspection) - The 4 HPs were removed and replaced with 6 HPs. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521 Install ladders per manufacturer instructions. - Observed a loose ladder and a loose hand rail. CDI - items were tightened during the inspection. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. - Observed a missing fitting on the fill port. CDI - fitting was replaced. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
.2626(k) Provide shatterproof mirrors. |