6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7.
Observed vacuum line with no plug at start of inspection. Observed gpm listed within permit restrictions (65 gpm to 98 gpm) not met at start of inspection. CDI - CPO acquired properly fitting vacuum line plug and screwed into fitting prior to end of inspection. CPO adjusted RPM on motor; gpm as read on flow meter was observed at approximately 70 gpm prior to end of inspection. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide at least 12 ft. long pole with body hook securely attached.
.2530(a) Pole for body hook must be non-telescoping, non-adjustable, and non-collapsible.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Observed ring buoy rope at 26’ at start of inspection (permit requires 27’ rope.) Observed telescoping body hook pole with push button tabs for hook. CDI - CPO made body hook pole non collapsible via screws and bolts placed through telescoping portion of pole. Hook was solidly attached to pole via screw and bolt. Ring buoy rope was unknotted by CPO such that length of 27’ was achieved. |