Premises Information

Return to Inspections
NamePRESERVATION POINTE
Address2710 HIGHWORTH LN
 
City/State/ZIP
CHARLOTTE NC 28214
Premise Type50 - Seasonal Swimming Pool
CountyMecklenburg
Inspection Date 4/21/2025
Final Score @ Grade
20
General CommentsNo night swimming. Inspection conducted with CPO Pamela and Aron Both stick feeder chlorinator approved No permit restrictions.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No .2518(k) Replace missing weirs. Observed 2 out of 4 weirs missing. CDI - CPO installed both missing weirs
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No Observed both hand rails extremely loose on both ends and ladder also extremely loose and not secured. CDI - CPO was able to secured both handrails and ladders.
12 4 Pool maintenance: inlets and other fittings in place and in good repair No No No .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed four face plates loose and not secured. CDI -CPO secured all face plates for handrails and ladders
15 6 Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located No No No .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed 1 out 2 ring buoy ropes at 45ft CDI - CPO reduced rope length to 39ft.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No .2518(g) Keep flow meter operational. Observed flow meter reading 0GPM and not moving at all. CDI - CPO installed new flow meter which resulted in 140GPM.