Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Observed main drains are different from the current PDSC form (submitted in 2020) PDSC states Aquastar 12MF101 and it appears they are now Aquastar WAV’s but unable verify the size. In addition, PDSC states 4 equalizers, however during the inspection equalizers are no longer on the pool walls. CPO stated that the pool was just plastered, so it appears the equalizer holes on the wall were plastered. Ensure that all skimmer equalizer lines are plugged and stated on the new PDSC form. Submit a new PDSC form to the health department. Permit Denial issued. |