Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539 - Observed one equalizer line in skimmer below basket plugged. CPO indicated that this was done during repairs. Other equalizers are unblocked and operable. CPO removed plug during inspection. - Corrected. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Replace missing weirs.
1 of 3 weirs missing. CPO replaced during inspection - Corrected. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Ring buoy throw rope observed at 46ft. CPO cut down rope to 33ft - Corrected. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
Observed no forced or cross ventilation in pump room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
.2526(k) Provide shatterproof mirrors. Observed mirrors not shatterproof. |