Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present. One gate was 2 sides and after you open one side (with proper closing mechanism) you can open the other side with a metal bar. It would not meet the self-close, self-latch requirement. This side of the gate was bolted to the fence essentially making it part of the fence. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
.2518(e) Provide a spare basket for pump. Spare basket was missing. Obtained. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed some water on the floor of the pump room. No visible leaks observed and equipment is all functioning properly.
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Pump room does not have forced/continuous ventilation. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
.2513(b) Filter backwash shall be discharged through an air gap. No air gap. |