Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Observed 2 Aquastar 1216 drain covers in pool. PDSC stated that the drain covers are Aquastar R12MF. Drains to not match. Permit denied. New PDSC form will need to be submitted and approved prior to permitting. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521 Install ladders per manufacturer instructions. Observed Handrail on steps loose and not secured. CDI: CPO tightened and secured handrail. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed one eyeball fitting missing on return. CDI: CPO installed and secured eyeball fitting to return. |