6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.
GPMs exceeding suction hazard restriction. CPO corrected to required setting of less than 385 gpm, at 340 gpm. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521 Install ladders per manufacturer instructions.
One ladder missing one end cap. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
One rope with length of rope less than 50ft. CPO corrected rope by providing new, cuttting and knotting to required length. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present.
Main gate not closing fully at start of inspection. CPO adjusted gate during inspection. EHS verified. |