3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
.2535(1) Maintain pH at 7.2 to 7.8. pH observed at 6.8, corrected with soda ash to 7.2 |
|
9
|
4
|
Pool maintenance: depth markings and no diving markers or signs visible and properly located |
No |
No
|
No |
.2523(b) Provide depth markers spaced not to exceed 25 feet when measured along the perimeter of the pool. Observed 3 ft depth marker distance on pool wall to be 26 ft 9" between next 3ft marker. PO added temporary adhesive depth marker. Needs more permanent depth marker ASAP and before next pool season. Oberved one pool deck depth marker to read 3 TF, need to say FT. PO corrected depth marker with adhesive depth marker. Need more permanent depth marker ASAP and before next pool season. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Pool phone number on sign not readable. PO corrected phone number to be readable. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed leak from capped pipe of sandfilter leaving pump room floor with some standing water. Leak needs repair.
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Ceiling exhaust fan in chem storage room appears non-working, not enough ventilation for natural cross ventilation. Provide proper ventilation. |
|
31
|
2
|
Dressing and sanitary facilities: sewage disposed of in a properly operating sewage system |
No |
No
|
No |
.2513(a) Sewage shall be disposed of in a public sewer. Appears backwash water is backing up into pump room floor drain basin. Sewer pipes possibly clogged, needs repair. |