Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameCOVINGTON AT PROVIDENCE
Address10620 FULLER RIDGE CIR
 
City/State/ZIP
CHARLOTTE NC 28276
Premise Type50 - Seasonal Swimming Pool
CountyMecklenburg
Inspection Date 4/13/2021
Final Score @ Grade
18
General CommentsNight swimming not permitted.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
3 6 Water quality: pool water pH No No No .2535(1) Maintain pH at 7.2 to 7.8. Pool water pH 7.0. Corrected to 7.2 during inspection.
6 6 Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ No No No .2539 - Observed all equalizer lines plugged with covers at beginning of inspection. PDSC does not indicate any equalizer lines plugged. Operator noted that they just took over this pool this season and that covers were in place from previous season. All plugs removed during inspection. REPEAT finding from previous pool season.
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No .2537(14) Keep pool surface and pool floor free of debris. Pool walls at all ladders with algae growth observed.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. Pool constructed May 2004. Chemical storage room present but not utilized. Bags and buckets of chemicals stored in pump room .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. Chemicals stored in pump room restricting access - less than 3 ft of clearance.