Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Cyanuric acid and total alkalinity not recorded weekly. Record weekly. Tested during inspection. CYA below 100 ppm. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form shows EQ lines not plugged with covers. Plugged at time of inspection. Plugs removed during inspection. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some algea on pool ladders. Continue to monitor so as to prevent an algea bloom. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
One return plugged. Plug removed and fitting replaced during inspection. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy rope degrading. Replaced with 50 ft. rope during inspection. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Observed >1/2" between post and gate at entry gate. Corrected with plexiglas during the inspection.
Fence height 45" from ground due to landscaping measured from outside. Pool built pre-2010. Pool fence shall be at least 48". |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
No dialing instructions at emergency phone. Corrected during inspection. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals stored in pump room. Pools built after April 1, 2004 shall provide a separate chemical storage room. Pool built May 2004.
Less than 3 ft. clearance around equipment in pump room due to storage and chemicals in pump room. Provide 3 ft. clearance around all equipment. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Hose bib in women's restroom missing backflow prevention device. Provide backflow prevention device on hose bib. |