Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameGILEAD VILLAGE
Address13515 SWINTON DR
 
City/State/ZIP
HUNTERSVILLE NC 28078
Premise Type50 - Seasonal Swimming Pool
CountyMecklenburg
Inspection Date 4/22/2026
Final Score @ Grade
16
General CommentsPermit restrictions: Flow meter must remain operable. Flow shall be kept at 79 gpm to 120 gpm to meet turnover and flow restriction of number of returns. Flow greater than 184 exceeds equalizer line flow. Suction Hazard. No Night swimming Inspection conducted with CPO Danielle Parker General Comment: Installation for 5% flow meter was approved. Verified the following for approval: 1. The flow meter is installed with proper pipe lengths before and after. 2. The current flow reading (gpm) meets the requirements based on notes from field book/dashboard.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Observed new record books present without space for documenting total alkalinity weekly. CDI: total alkalinity space manually written in book until fixed permanently.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed skimmers and baskets with debris. CDI: cleaned on site by CPO.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. Observed some areas in fence height about < 48”. Pool built prior to 2010. No permit action. Point demerits.
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No .2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed some lawn chairs as close as 4-5ft from pool edge. CDI: chairs moved back to provide 6ft clearance.