11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521 Install ladders per manufacturer instructions. Both ladders loose and missing end caps.
.2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. Ladder at far side of pool distance between rungs and wall greater than 6”. End of ladder without end caps on this ladder could present sharp edge hazard for swimmers ad sufficient space for body part between ladder end and wall.
Operator replaced end caps. EHS recommends repairing or replacing ladder to ensure rungs are between 3” and 6” from wall to ensure no areas for entrapment. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy rope tangled/knotted such that is less than 50’ and would not be easily usable in emergency. Operator replaced with new 50’ rope. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Furniture within 6’ of edge of pool. Relocated away from pool. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Signage providing address of pool faded / not clearly legible. Operator corrected during inspeciton. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(b) Provide sufficient lighting in pump room. Light fixture not working in pump room.
Unable to determine if vent fan in pump room is operating. |