Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Pool has been re-plastered and equalizer covers have been removed and lines have been disabled. EHS verified equalizers have been plastered over on pool wall and plugged inside of the skimmers. PDSC documentation has not been provided showing updated pool drain suction compliance. Operator completed and submitted updated PDSC form during inspection. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy with no rope attached. Operator attached 50’ rope as required. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2537(b) All gates and doors shall be self-closing, self-latching. Gate near clubhouse not self latching. Gate near gazebo does not always self close and latch. Both corrected by operator during inspection. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
.2526(m) Keep restrooms and fixtures clean and in good repair. Fixtures in both restrooms with no water at this time. Plumber on site repairing due to complete work today. Ensure hot water temperature remains at 110f or less once water is restored. |